Specifications
Valve specifications
- Pattern
 - 2-way
 - V'nom [l/s]
 - 1.67
 - Flow rate adjustable
 - 25...100% of V'nom
 - Fluid
 - Water, water with glycol up to max. 60% vol.
 - Fluid temperature
 - -10...120°C [14...248°F]
 - Fluid temperature note
 - 
    
- At a fluid temperature of -10...2°C, a stem heater or a valve neck extension is recommended.
 - The allowed fluid temperature can be limited, depending on the type of actuator. Limitations can be found in the respective data sheets of the actuators.
 
 - Close-off pressure
 - 1400Â kPa
 - Differential pressure note
 - 200 kPa for low-noise operation
 - Flow characteristic {Tools}
 - Equal percentage
 - Leakage rate {Tools}
 - Air-bubble tight, leakage rate A
 - Pipe connection
 - Internal and external thread
 
Actuator specifications
- Voltage AC/DC
 - AC/DCÂ 24Â V
 - Power consumption (running)
 - 5 W
 - Power consumption (holding)
 - 3.9 W
 - Power Consumption For Wire Sizing
 - 7.5 VA
 - Connection Supply Control
 - Cable 1 m, 6x 0.75 mm²
 - Connection Ethernet
 - RJ45 socket
 - Control type
 - 
    
- BACnet/IP
 - BACnet MS/TP
 - Modbus TCP
 - Modbus RTU
 - MP-Bus
 - DCÂ 2...10Â V
 - DCÂ 0.5...10Â V
 - Hybrid (communicative / analogue)
 - Cloud
 
 - Protection category
 - IP54